Basic Info.
Frequency Characteristics
High Frequency
Power Source
High Frequency AC Power Supply
Application Range
Industrial and Mining Enterprises
Transport Package
Wooden Case
Product Description
Features
FPGA digital control, intelligent inverter testing process;
High performance low (zero) voltage ride through;
Voltage and frequency can be set as complex programming such as Step, List or Ramp, overvoltage/undervoltage, over-frequency/under-frequency test;
Harmonic mode, superimposed 2 to 40-th harmonics;
Unbalanced mode, adjustable three-phase voltage and three-phase phase difference, Unbalanced test;
High voltage DC output. Loop test combining PV inverter;
3 times of rated current impact withstand for 2S, strong load capacity;
Complete measurements: voltage, current, peak current, frequency, active power, apparent power, power factor, voltage crest factor;
Online monitoring: IGBT temperature, transformer temperature, fan speed, input voltage and other parameters in output state;
Operating data recorder: Automatically record the power status, alarm code etc. in case of alarm, greatly reducing maintenance time;
Automatic fan speed adjustment according to the temperature of the power supply, quiet;
Lock key, user-friendly design, automatically locking after no-operation for 5 minutes to prevent misuse;
8" color LCD, beautiful appearance;
Standard professional PC control software and RS232 port, optional RS485, GPIB, Ethernet port or analog control mode;
Order and extensions
ANGS Grid Simulator Power Supply supply: 0.0 ~ 300.0V/45.00 ~ 65.00Hz, optional 15kVA, 30kVA, 45kVA, 60kVA, 90kVA, 120kVA, 180kVA, 240kVA, 400kVA, 500kVA, 750kVA, 1000kVA.
Standard PC control software.
Communication Interface: Standard RS-232 port, optional RS-485, GPIB, Ethernet (Note: choose any one of RS-232, RS-485, GPIB, Ethernet). Note in order.
Remote control: Optional analog control.
PC control software
Applications
The ANGS series Grid Simulator Power Supply can simulate overvoltage/undervoltage, over-frequency/under-frequency, low (zero) voltage ride through and other curves. The overvoltage/undervoltage, over-frequency/under-frequency, anti-islanding protection of inverter can be tested with anti-islanding load or AC electronic load. AN51 series solar cell simulator can simulate a variety of I-V curves of solar cell to verify the inverter's maximum power tracking capability, and conduct inverter aging test and overvoltage/undervoltage protection; AN87500 multi-channel power analyzer can analyze the inverter's power, harmonics, efficiency and other parameters, so as to conduct comprehensive analysis of inverter performance. Three kinds of equipment can be integrated using professional PC test software to form a comprehensive inverter test system and solutions.
The DC output terminal of ANGS series Grid Simulator Power Supply is connected to the DC input terminal of the inverter. The DC output terminal of the inverter is connected with the output terminal of the Grid Simulator Power Supply in parallel to form a loop test. The energy flows in the loop, saving equipment investment for some specific tests.
Specifications of ANGS series
Model | ANGS015T | ANGS030T | ANGS045T | ANGS060T | ANGS090T | ANGS120T | ANGS180T | ANGS240T | |
Capacity | 15kVA | 30kVA | 45kVA | 60kVA | 90kVA | 120kVA | 180kVA | 240kVA | |
AC input | Number of phases | Three-phase four-wire + PE | |
Voltage | Phase voltage: 220V ± 33V, line voltage: 380V ± 57V | |
Frequency | 50/60Hz±3Hz | |
AC output | Number of phases | Three-phase four-wire | |
Mode | Standard, Unbalanced | |
Voltage | Phase voltage: 0.0 ~ 300.0V | |
Frequency | 45.00~65.00Hz | |
Rated current | 220V | 22.7A | 45.4A | 68.2A | 90.9A | 136.3A | 181.8A | 272.7A | 363.6A | |
Setting accuracy | Voltage | Resolution: 0.1V. Accuracy: 0.2%× reading +0.2%× Full scale | |
Frequency | Resolution: 0.01Hz. Accuracy: 0.05% | |
Measurement accuracy | Voltage | Resolution: 0.1V. Accuracy: 0.2%× reading +0.2%× Full scale | |
Frequency | Resolution: 0.01Hz. Accuracy: 0.05% | |
Current | Resolution: 0.1A/1A. Accuracy: 0.3%× display +0.3%× Rated output | |
Power | Resolution: 0.1kW/0.01kW/0.001kW. Accuracy: 0.45%× reading +0.45%× Full scale | |
Frequency stability | ≤0.02% | |
Voltage distortion | Linear load: THD<1% | |
Transient recovery time | 20ms | |
Three-phase phase difference | Standard: 120±2° Unbalanced: 0.0~359.9°, 0.1° adjustable | |
|
Phase voltage crest factor | 1.41±0.1 | |
Source voltage effect | ≤1% | |
Load effect | ≤1% | |
Overload capability | 105%< output ≤110%: Cut off the output within 15S; 110%< output ≤200%: Cut off the output within 5S 200%< output ≤300%: Cut off the output within 2S; 300%< output: Cut off the output immediately | |
|
Impact resistance | (1) Withstand 3 times the rated current for 2S; (2) Withstand inductive load with power not more than 0.5 times the rated power or start-up impact of rectifier load with crest factor less than 3.0 | |
|
Protection | IGBT overheating, IGBT overcurrent, transformer overheating, input overvoltage/undervoltage, output overvoltage/undervoltage, output phase failure, output overcurrent, output overload, output short circuit, bus anti-recharge | |
|
Efficiency | >86% | |
Function | Display | 8" LCD, resolution: 800 * 600 | |
Output waveform | Sine wave, harmonics (superimposed 2 ~ 40-th harmonics) | |
Programming | Low (zero) voltage through | With, minimum response time 20ms | |
Step | Step: 9999 | |
List | 100 steps: 999999 cycles | |
Ramp | 100 steps: 999999 cycles | |
Start ramp time | 0.0 ~ 99.9 seconds | |
Online regulation | Output voltage, output frequency in normal mode, online switching of waveform | |
Memory | Power-off memory, store the last output mode and parameters | |
Shortcuts | 10 groups of common modes, 10 groups of harmonics | |
Line voltage drop compensation | 0.000~0.500Ω | |
Communication ports | RS232 (standard), RS485 (optional), GPIB (optional), Ethernet (optional), Flip signal (standard) | |
Remote control | Analog control port (optional) | |
DC output | Voltage | DC bus voltage | |
Current | 16A | 33A | 49A | 65A | 98A | 131A | 196A | 262A | |
Working environment | Temp. | 0~40ºC | |
Humidity | 20~90%RH | |
Dimension W*H*D (mm) | 1000×1990×800 | 1200×1990×800 | 1200×1990×1000 | |
Weight (KG) | 310 | 360 | 500 | 620 | 810 | 1060 | 1280 | 1380 | |
Model | ANGS400T | ANGS500T | ANGS750T | ANGS1000T | |
Capacity | 400kVA | 500kVA | 750kVA | 1000kVA | |
AC input | Number of phases | Three-phase four-wire + PE | |
Voltage | Phase voltage: 220V ± 33V, line voltage: 380V ± 57V | |
Frequency | 50/60Hz±3Hz | |
AC output | Number of phases | Three-phase four-wire | |
Mode | Standard, Unbalanced | |
Voltage | Phase voltage: 0.0 ~ 300.0V | |
Frequency | 45.00~65.00Hz | |
Rated current | 220V | 606A | 757A | 1136A | 1515A | |
Setting accuracy | Voltage | Resolution: 0.1V. Accuracy: 0.4%× reading +0.4%× Full scale | |
Frequency | Resolution: 0.01Hz. Accuracy: 0.05% | |
Measurement accuracy | Voltage | Resolution: 0.1V. Accuracy: 0.4%× reading +0.4%× Full scale | |
Frequency | Resolution: 0.01Hz. Accuracy: 0.05% | |
Current | Resolution: 0.1A/1A. Accuracy: 0.4%× display +0.4%× Rated output | |
Power | Resolution: 0.1kW/0.01kW/0.001kW. Accuracy: 0.7%× reading +0.7%× Full scale | |
Frequency stability | ≤0.02% | |
Voltage distortion | Linear load: THD<3% | |
Transient recovery time | 20ms | |
Three-phase phase difference | Standard: 120±2° Unbalanced: 0.0~359.9°, 0.1° adjustable | |
|
Phase voltage crest factor | 1.41±0.1 | |
Source voltage effect | ≤2% | |
Load effect | ≤2% | |
Overload capability | 105%< output ≤110%: Cut off the output within 15S; 110%< output ≤200%: Cut off the output within 5S 200%< output ≤300%: Cut off the output within 2S; 300%< output: Cut off the output immediately | |
|
Impact resistance | (1) Withstand 3 times the rated current for 2S; (2) Withstand inductive load with power not more than 0.5 times the rated power or start-up impact of rectifier load with crest factor less than 3.0 | |
|
Protection | IGBT overheating, IGBT overcurrent, transformer overheating, input overvoltage/undervoltage, output overvoltage/undervoltage, output phase failure, output overcurrent, output overload, output short circuit, bus anti-recharge | |
|
Efficiency | >86% | |
Function | Display | 8" LCD, resolution: 800 * 600 | |
Output waveform | Sine wave, harmonics (superimposed 2 ~ 40-th harmonics) | |
Programming | Low (zero) voltage through | With, minimum response time 20ms | |
Step | Step: 9999 | |
List | 100 steps: 999999 cycles | |
Ramp | 100 steps: 999999 cycles | |
Start ramp time | 0.0 ~ 99.9 seconds | |
Online regulation | Output voltage, output frequency in normal mode, online switching of waveform | |
Memory | Power-off memory, store the last output mode and parameters | |
Shortcuts | 10 groups of common modes, 10 groups of harmonics | |
Line voltage drop compensation | 0.000~0.500Ω | |
Communication ports | RS232 (standard), RS485 (optional), GPIB (optional), Ethernet (optional), Flip signal (standard) | |
Remote control | Analog control port (optional) | |
DC output | Voltage | DC bus voltage | |
Current | 436A | 545A | 818A | 1091A | |
Working environment | Temp. | 0~40ºC | |
Humidity | 20~90%RH | |
Dimension W*H*D (mm) | 3600×2000×1000 | 4800×2000×1000 | 6000×2000×1000 | |
Weight (KG) | 3050 | 3380 | 4870 | 6360 | |
Address:
No. 134 Zhuzhou Rd, Qingdao, Shandong, China
Business Type:
Manufacturer/Factory, Trading Company, Other
Business Range:
Electrical & Electronics
Management System Certification:
ISO 9001
Company Introduction:
We Ainuo Intelligent Instrument Co., Ltd are a professional designer and manufacturer of test machines, power supply equipment, automatic test system, etc., were established in 1993. We are expert in supplying solution for institutes of Quality Inspection, Commodity Inspection and Measurement dept & industries of electrical appliance, power supply and motor manufacturing industries.
Ainuo mainly has 10 product series:
1. Photovoltaic and Inverter Test Solution;
2. Battery test solution;
3. Power supply test solution;
4. Household appliance test solution;
5. Motor and transformer test solution;
6. Aviation power supply and test solution;
7. Special power supply and test solution;
8. Electrical safety test solution;
9. Power electronics test solution;
10. Quality Inspection Institute Test Solution.
We have won the long-term trust and cooperation of up to several tens of thousand of clients, such as Haier, Media, Gree, Hisense, Changhong, AOC, GE, Electrolus and so on.
Ainuo mission is to "Be an enterprise with great sense of responsibility in the world"